Quinn (previously known as Barlo) Designer Radiators - General Specifications and Information
Product Range.
The Quinn Designer radiator range comprises of the following designs
Primo |
Forza |
||
Adagio |
|
||
Opus 1 |
Opus 2
|
||
Quality. All radiators are manufactured under a BS EN ISO 9001: 2000 quality system accepted by BSI.
Warranty.
All radiators are supplied under warranty for five years in respect of defective materials and manufacture.Packaging.
Each radiator is securely packaged to provide sufficient protection for transportation within the UK.Outputs and Conversion Information.
All radiators have been manufactured and tested in accordance with BS EN 442. The outputs quoted in for each model are based on a Delta T of 50°C. To calculate output other operating conditions use the following method to calculate the required delta T value then from the table below select the factor to apply to the output provided for the particular productMethod;-
a. Add the flow water temperature and the return water temperature together.
b. Divide the answer from a. by 2
c. From the answer b. subtract the room temperature. This gives your 'delta T' temperature
d. Select the closest delta T value to your from the table and multiply the corresponding factor by the output provided for the particular radiator to obtain the output for your calculated delta T value.
| Delta T | Factor | Delta T | Factor | Delta T | Factor |
| 5°C | 0.0501 | 30°C | 0.5148 | 55°C | 1.1319 |
| 10°C | 0.1234 | 35°C | 0.6290 | 60°C | 1.2675 |
| 15°C | 0.2091 | 40°C | 0.7482 | 65°C | 1.4065 |
| 20°C | 0.3039 | 45°C | 0.8720 | 70°C | 1.5487 |
| 25°C | 0.4061 | 50°C | 1.0000 | 75°C | 1.6940 |
Connections.
All radiators are manufactured with 1/2" BSP BOE connections, except Opus 1 and Opus 2, which have connections at BBOE.Installation.
For indirect systems or closed circuits only at a working pressure not exceeding 5.38 bar (78 psi)Water Treatment.
It is strongly recommended on completion of the installation, the system should be properly flushed and filled in accordance with the British Standard Code of Practice for the Treatment of Water in Domestic Hot Water Central Heating Systems BS 7593. Use of a corrosion inhibitor is strongly recommended by the manufacturer. Failure to observe this recommendation will invalidate the manufacturer's warranty.